6181 B
Installation in wall, on boards and in channels or embedded in plaster. Low level of smoke emission and corrosive gasses in case of fire.
1- Conductor : Solid or stranded copper (Class 1 or Class 2)
2- Insulation : Cross linkable polyethylene (XLPE)
3- Outer sheath : Low smoke zero halogen (LSZH)
| Min. bending radius |
x D ≤ 25 mm² |
| Max. operating temperature |
90° |
| Max. short circuit temperature |
250° |
| Min. bending radius |
12 x D > 25 mm² |
| Rated voltage Uo/U |
450/750 V - 600/1000 V |
| AC test voltage |
2,5 kV - 3,5 kV |
| Low smoke |
EN 61034 |
| Halogen free |
EN 50525-1 - EN 50267 |
| Flame propagation test on single cable |
EN 60332-1 |
| Nominal Cross Section mm² |
Overall Diameter mm approximately |
Net Weight kg/km approximately |
Conductor DC Resistance at (20°C) max. ohm/km |
Current Carrying Capacity in |
| Conduit (A) |
| 6181 B |
| 1,5 |
4,4 |
31 |
12,1 |
23 |
| 2,5 |
4,8 |
42 |
7,41 |
31 |
| 4* |
5,7 |
63 |
4,61 |
42 |
| 6* |
6,2 |
83 |
3,08 |
54 |
| 10* |
7,3 |
125 |
1,83 |
75 |
| 16* |
8,5 |
183 |
1,15 |
100 |
| 25* |
9,7 |
276 |
0,727 |
133 |
| 35* |
10,9 |
374 |
0,524 |
164 |
| 50 |
13,2 |
522 |
0,387 |
198 |
| 70 |
14,7 |
722 |
0,268 |
253 |
| 95 |
17,2 |
997 |
0,193 |
306 |
| 120 |
19,1 |
1244 |
0,153 |
354 |
| 150 |
20,8 |
1515 |
0,124 |
393 |
| 185 |
23,0 |
1890 |
0,0991 |
449 |
| 240 |
26 |
2441 |
0,0754 |
528 |
| 300 |
28,8 |
3124 |
0,0601 |
603 |