6181 XY
Installation in walls, on boards and in channels or embedded in plaster.
1- Conductor : Solid or stranded copper (Class 1 or Class 2)
2- Insulation : Cross linkable polyethylene (XLPE)
3- Outer sheath : Polyvinyl chloride (PVC)
| Min. bending radius |
4 x D ≤ 25 mm² |
| Max. operating temperature |
90° |
| Max. short circuit temperature |
250° |
| Min. bending radius |
6 x D > 25 mm² |
| Rated voltage Uo/U |
600/1000 V |
| AC test voltage |
2,5 kV - 3,5 kV |
| Flame propagation test on single cable |
EN 60332-1 |
| Lead free |
Pb |
| Nominal Cross Section mm² |
Overall Diameter mm approximately |
Net Weight kg/km approximately |
Conductor DC Resistance at (20°C) max. ohm/km |
Current Carrying Capacity in |
| Conduit (A) |
| 6181 XY |
| 1,5 * |
4,4 |
31 |
12,2 |
23 |
| 2,5 * |
4,8 |
42 |
7,41 |
31 |
| 4 * |
5,7 |
63 |
4,61 |
42 |
| 6* |
6,2 |
83 |
3,08 |
54 |
| 10* |
7,1 |
124 |
1,83 |
75 |
| 16* |
8,4 |
188 |
1,15 |
100 |
| 25* |
9,9 |
281 |
0,727 |
133 |
| 35* |
10,9 |
374 |
0,524 |
164 |
| 50* |
13,0 |
518 |
0,387 |
198 |
| 70* |
14,7 |
723 |
0,268 |
253 |
| 95* |
16,6 |
973 |
0,193 |
306 |
| 120* |
18,5 |
1217 |
0,153 |
354 |
| 150* |
20,4 |
1495 |
0,124 |
393 |
| 185* |
22,2 |
1848 |
0,0991 |
449 |
| 240* |
25,4 |
2404 |
0,0754 |
528 |
| 300* |
28,9 |
3125 |
0,0601 |
603 |