6181 Y
Installation in walls, on boards and in channels or embedded in plaster.
1- Conductor : Solid or stranded copper (Class 1 or Class 2)
2- Insulation : Polyvinyl chloride (PVC)
3- Outer sheath : Polyvinyl chloride (PVC)
| Min. bending radius |
8 x D ≤ 25 mm² |
| Max. operating temperature |
70° |
| Max. short circuit temperature |
160° |
| Min. bending radius |
12 x D > 25 mm² |
| Rated voltage Uo/U |
300/300 V |
| AC test voltage |
2 kV |
| Flame propagation test on single cable |
EN 60332-1 |
| Lead free |
Pb |
| Nominal Cross Section mm² |
Overall Diameter mm approximately |
Net Weight kg/km approximately |
Conductor DC Resistance at (20°C) max. ohm/km |
Current Carrying Capacity in |
| Conduit (A) |
| 6181 Y |
| 1* re |
3,9 |
26 |
18,1 |
13,5 |
| 1,5* re |
4,4 |
33 |
12,1 |
19,5 |
| 2,5* re |
5,0 |
46 |
7,41 |
24 |
| 4* rm |
6 |
69 |
4,61 |
32 |
| 6* rm |
6,5 |
89 |
3,08 |
41 |
| 10* rm |
7,8 |
139 |
1,83 |
57 |
| 16* |
9,1 |
207 |
1,15 |
76 |
| 25* |
11 |
312 |
0,727 |
101 |
| 35* |
12,1 |
410 |
0,524 |
125 |
| 50 |
13,8 |
557 |
0,387 |
151 |
| 70 |
15,6 |
761 |
0,268 |
192 |
| 95 |
18,2 |
1060 |
0,193 |
232 |
| 120 |
19,9 |
1307 |
0,153 |
269 |
| 150 |
21,8 |
1599 |
0,124 |
300 |
| 185 |
23,8 |
1977 |
0,0991 |
341 |
| 240 |
27,8 |
2608 |
0,0754 |
400 |
| 300 |
32,5 |
3355 |
0,0601 |
458 |