Productions

6381 Y

Installation in walls, on boards and in channels or embedded in plaster.
1- Conductor : Solid or stranded copper (Class 1 or Class 2)
2- Insulation : Polyvinyl chloride (PVC)
3- Outer sheath : Polyvinyl chloride (PVC)
Min. bending radius 8 x D ≤ 25 mm² 
Max. operating temperature 70°
Max. short circuit temperature 160°
Min. bending radius 12 x D > 25 mm² 
Rated voltage Uo/U 300/300 V - 600/1000 V
AC test voltage 2,5 kV - 3,5 kV
Flame propagation test on single cable EN 60332-1
Lead free Pb
Nominal Cross Section mm²  Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Air (A)
6381 Y
4* 6,9 82 4,95 32
6* 7,4 104 3,30 41
10* 8,9 157 1,91 57
16* 10,0 220 1,21 76
25* 12,2 330 0,780 101
35* 13,4 431 0,554 125
50 14,9 575 0,386 151
70 16,6 764 0,272 192
95 19,5 1033 0,206 232
120 20,6 1265 0,161 269
150 23,0 1572 0,129 300
185 26,2 1931 0,106 341
240 29,0 2470 0,0801 400
300 31,8 3067 0,0641 458
400 39,2 4148 0,0486 546
AVESCON
2025 PRODUCT CATALOGUE
Click here to view our product catalog.