| Parameter | Unit | Value |
|---|---|---|
| Aluminium Alloy Wire Diameter | mm | 3.00 ± 0.03 |
| Aluminium Clad Steel Wire Diameter | mm | 3.00 ± 0.05 |
| O/F Stainless Steel Tube Diameter | mm | 3.00 ± 0.05 |
| OPGW Conductor Diameter | mm | 15.00 ± 0.5 |
| Number of Aluminium Clad Steel Wire | center | 1 |
| Number of Aluminium Clad Steel Wire | 1st Layer | 5 |
| Number of Stainless Steel Tube | 1st Layer | 1 |
| Number of Aluminium Alloy (AAA) Wire | 2nd Layer | 8 |
| Number of Aluminium Clad Steel Wire | 2nd Layer | 4 |
| Lay Direction | 1st Layer | Left-Hand (S-twist) |
| Lay Direction | 2nd Layer | Right-Hand (Z-twist) |
| Total OPGW Cross-Section | mm² | 134.3 |
| Aluminium Alloy Unit Weight | kg/km | 152.8 |
| Aluminium Clad Steel Wire Unit Weight | kg/km | 465.6 |
| O/F Tube and Jelly Unit Weight | kg/km | 16.0 |
| Total OPGW Unit Weight | kg/km | 634.4 |
| OPGW Rated Tensile Strength (RTS) | daN | 10700 |
| Final Modulus Elasticity of OPGW | daN/mm² | 11200 |
| Thermal Expansion Coefficient of OPGW | 10⁻⁶/°C | 15.1 |
| Permissible Max. Working Stress | daN | 4280 |
| Medium High Tension | daN | 1712 - 2675 |
| Endurance Tensile Strength (ETS) | daN | 7490 |
| Short Time Overcurrent (0.5 second) (40-180°C) | A | 14600 |
| Temperature After Short Time Overcurrent | °C | 180 |
| Working Temperature (Max.) | °C | 80 |
| Resistance at 20 °C (Max.) | ohm/km | 0.540 |
| O/F Stainless Steel Tube Diameter (Inner/Outer) | mm | 2.6 / 3.0 |
| Fiber Count | - | 12 - 24 |
| Working Temperature | °C | -40 ile 80 |