H03VVH2-F / HO5VVH2-F
Used in dry and humid areas that there are not much mechanical compulsion in which, generally used in household equipments.
1- Conductor : Fine-stranded copper (Class 5)
2- Insulation : Polyvinyl chloride (PVC)
3- Outer sheath : Polyvinyl chloride (PVC)
| Min. bending radius |
D≤12 ise 5D - D>12 ise 6D |
| Max. operating temperature |
60° |
| Max. short circuit temperature |
150° |
| Rated voltage |
300/300 V - 300/500V |
| AC test voltage |
2 kV |
| Flame propagation test on single cable |
EN 60332-1 |
| Lead free |
Pb |
| Nominal Cross Section mm² |
Overall Diameter mm approximately |
Net Weight kg/km approximately |
Conductor DC Resistance at (20°C) max. ohm/km |
Current Carrying Capacity in |
| Air (A) |
| H03VVH2-F (300/300 V) / 219Y |
| 2x0,50 |
3,1 x 5,0 |
30 |
39,0 |
3 |
| 2x0,75 |
3,4 x 5,5 |
37 |
26,0 |
6 |
| H05VVH2-F (300/500 V) / 319Y |
| 2x0,75 |
4,0 x 6,3 |
47 |
26,0 |
6 |
| 2x1 |
4,1 x 6,6 |
54 |
19,5 |
10 |
| 2x1,5 |
4,7 x 7,6 |
73 |
13,3 |
16 |
| 2x2,5 |
5,6 x 9,1 |
108 |
7,98 |
25 |
| 2x4 |
6,3 x 10,4 |
150 |
4,95 |
32 |
| 3x0,75 |
4,0 x 8,7 |
66 |
26,0 |
6 |
| 3x1 |
4,1 x 9,1 |
76 |
19,5 |
10 |
| 3x1,5 |
4,7 x 10,5 |
103 |
13,3 |
16 |
| 3x2,5 |
5,8 x 12,9 |
108 |
7,98 |
25 |
| 3x4 |
6,5 x 14,7 |
220 |
4,95 |
32 |