1- Conductor : Fine-stranded copper (Class 5)
2- Insulation : Cold resistant polyvinyl chloride (CR-PVC)
Min. bending radius D<8 ise 4xD   812 ise 6xD
Max. operating temperature 70°
Max. short circuit temperature 160°
Rated voltage Uo/U 300/500 V - 450/750 V
AC test voltage 2 kV / 2,5 kV
Flame propagation test on single cable - EN 60332-1  EN 60332-1-2
Nominal Cross Section mm²  Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Conduit (A) Air (A)
H05V3-K (300/500 V)
0,50 2,1 9 39,0 - -
0,75 2,3 12 26,0 - 16
1 2,5 14 19,5 12 20
H07V3-K (450/750 V)
1,5 3,0 20 13,3 15 24
2,5  3,7 33 7,98 20 32
4,5 50 4,95 25 42
5,5 70 3,30 33 54
10  6,5 120 1,91 45 73
16  7,5 180 1,21 61 98
25  10,0 270 0,780 83 129
35  11,0 360 0,554 103 158
50  13,0 510 0,386 132 198
70  15,0 700 0,272 165 245
95  17,0 950 0,206 197 292
120  19,0 1150 0,161 235 344
150  21,0 1450 0,129 - 391
185  23,0 1750 0,106 - 448
240  27,0 2300 0,0801 - 528