H05V3-U / H07V3-U / H07V3-R
Installation in surface mounted or embedded conduits or similar closed systems at low temperatures.
1- Conductor : Solid or stranded copper (Class 1 or Class 2)
2- Insulation : Cold resistant polyvinyl chloride (HR-PVC)
| Min. bending radius |
D<8 ise 4xD 812 ise 6xD |
| Max. operating temperature |
70° |
| Max. short circuit temperature |
160° |
| Rated voltage Uo/U |
300/500 V - 450/750 V |
| AC test voltage |
2 kV / 2,5 kV |
| Flame propagation test on single cable - EN 60332-1 |
EN 60332-1-2 |
| Nominal Cross Section mm² |
Overall Diameter mm approximately |
Net Weight kg/km approximately |
Conductor DC Resistance at (20°C) max. ohm/km |
Current Carrying Capacity in |
| Conduit (A) |
Air (A) |
| H05V3-U (300/500 V) |
| 0,50 |
2,0 |
9 |
36,0 |
- |
- |
| 0,75 |
2,2 |
12 |
24,5 |
- |
15 |
| 1 |
2,4 |
15 |
18,1 |
11 |
19 |
| H07V3-U / H07V3-R (450/750 V) |
| 1,5 |
2,8 |
20 |
12,1 |
16 |
25 |
| 2,5 |
3,3 |
30 |
7,41 |
21 |
34 |
| 4 |
3,8 |
45 |
4,61 |
27 |
45 |
| 6 |
4,3 |
65 |
3,08 |
35 |
57 |
| 10 |
6,0 |
115 |
1,83 |
48 |
78 |
| 16 |
7,0 |
170 |
1,15 |
65 |
104 |
| 25 |
8,5 |
260 |
0,727 |
88 |
137 |
| 35 |
9,5 |
360 |
0,524 |
110 |
168 |
| 50 |
11,0 |
480 |
0,387 |
140 |
210 |
| 70 |
13,0 |
670 |
0,268 |
175 |
260 |
| 95 |
15,0 |
930 |
0,193 |
210 |
310 |
| 120 |
16,5 |
1160 |
0,153 |
250 |
365 |
| 150 |
18,0 |
1420 |
0,124 |
- |
415 |
| 185 |
20,0 |
1780 |
0,0991 |
- |
475 |
| 240 |
23,0 |
2330 |
0,0754 |
- |
560 |
| 300 |
26,0 |
2930 |
0,0601 |
- |
645 |
| 400 |
29,0 |
3750 |
0,0470 |
- |
770 |