Productions

H05Z-U / H07Z-U / H07Z-R

Installatıon in surface mounted or embedded conduits or similar closed systems. Low level of smoke emission and corrosive gases in case of fire
1- Conductor : Solid or stranded copper (Class 1 or Class 2)
2- Insulation : Low smoke zero halogen cross linkable (XL-LSZH)
Min. bending radius D<8 ise 4xD   812 ise 6xD
Max. operating temperature 90°
Max. short circuit temperature 250°
Rated voltage Uo/U 450/750 V
AC test voltage 2,5 kV
Low smoke EN 61034
Halogen free  EN 50525-1 - EN 50267
Flame propagation test on single cable - EN 60332-1 EN 60332-1-2
Nominal Cross Section mm²  Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Current Carrying Capacity in
Conduit (A) Air (A)
H07Z-U / H07Z-R (450/750 V) / 6491B
1,5  2,7  21 12,1  23 -
2,5  3,3 34 7,41 31 -
3,7 50 4,61 42 -
4,2 71 3,08 54 -
10 6,0 116 1,83 75 -
16 7,0 161 1,15 100 -
25 8,8 258 0,727 133 161
35  9,5 346 0,524 164 200
50  11,0 468 0,387 198 242
70  12,5 660 0,268 253 310
95  15,0 910 0,193 306 377
120  16,5 1140 0,153 354 437
150  18,0 1405 0,124 393 504
185  20,0 1745 0,0991 449 575
240  23,0 2295 0,0754 528 679
300  26,0 2900 0,0601 603 783
400 29,0 3700 0,0470 683 940
AVESCON
2025 PRODUCT CATALOGUE
Click here to view our product catalog.
download >