HO5V-U / HO7V-U / HO7V-R
Used in closed and dry areas, switch and distribution boards, fixed installations laying in conduit on and under plaster.
1- Conductor : Solid copper (Class1)
2- Insulation : Polyvinyl chloride (PVC)
|
Min. bending radius
|
D<8 ise 4xD 812 ise 6xD
|
| Max. operating temperature |
70° |
| Max. short circuit temperature |
160° |
| Rated voltage Uo/U |
300/500 V - 450/750 V
|
| AC test voltage |
2 kV / 2,5 kV |
| Flame propagation test on single cable - EN 60332-1 |
EN 60332-1-2 |
| Nominal Cross Section mm² |
Overall Diameter mm approximately |
Net Weight kg/km approximately |
Conductor DC Resistance at (20°C) max. ohm/km |
Current Carrying Capacity in |
| Conduit (A) |
Air (A) |
| H05V-U (300/500 V) / 2491X |
| 1x0,50 |
2,0 |
9 |
36 |
- |
- |
| 1x0,75 |
2,2 |
12 |
24,5 |
- |
16 |
| 1x1,0 |
2,4 |
13 |
18,1 |
11 |
19 |
| H07V-U (450/750V) / 6491X |
| 1x1,5 |
2,7 |
21 |
12,1 |
14,5 |
24 |
| 1x2,5 |
3,2 |
34 |
7,41 |
19,5 |
32 |
| 1x4 |
3,7 |
50 |
4,61 |
26 |
42 |
| 1x6 |
4,2 |
71 |
3,08 |
34 |
54 |
| 1x10 |
5,4 |
116 |
1,83 |
46 |
73 |