Productions

LI2Y(St)CY PIMF

In places where electro-magnetic interference and influence exists
Instrumentation and Control Engineering
Industrial Electronics
Computers and Office Machines
Automation Systems
High Transmission Rates In Data Processing Systems

NOTES
With their flexible design they can be easily used in narrow spaces.
These cables are not suitable for outdoor installations.
*EMC: Electromagnetic compatibility

Conductor IEC 60228; DIN VDE 0295; EN 60228 Class 2 or Class 5
Electrolytic Bare or Tinned Copper
Insulation EN 50290-2-23 PE Compound
Colour Code DIN 47100
Individual Screen Pes Tape + Tinned Copper Drain Wire + Pes Tape
Stranding Screened pairs in layers
Wrapping Pes Bant
Screen Tinned Copper Drain Wire + Al-Pes Tape + Tinned Copper Braid
Sheath EN 50290-2-22 PVC Compound
Sheath Colour RAL 7001 Grey
CONDUCTOR RESISTANCE INSULATION RESISTANCE
(500 V)
MUTUAL CAPACITY
(MAX)
IMPEDANCE
(APPROX.)
INDUCTANCE
(APPROX.)
CURRENT CARRYING
CAPACITY (25°C)
mm²
0,22
0,34
0,50
0,75
1,0
1,5
2,5
Ω/km
79
56
39
26
19,5
13,3
7,98
5000 MΩXKm mm²
0,22
0,34
0,50
0,75
1,0
1,5
2,5
pF/m
70
80
90
90
90
100
120
78Ω 0,67mH/km mm²
0,22
0,34
0,50
0,75
1,0
1,5
2,5
A
2,5
4,5
6,0
13
16
20
25


OPERATING VOLTAGE TEST VOLTAGE BENDING RADIUS TEMPERATURE RANGE FLAME RETARDANT TEST
0,22/0,34mm2 = 250V
>0,50mm2 = 300/500V
0,22/0,34mm2 = 1000V
0,50mm2 = 2000V
10x Cable Ø -30ºC~+70ºC IEC 60332-1-2
VDE 0482-322-1-2
EN 60332-1-2
AVESCON
2025 PRODUCT CATALOGUE
Click here to view our product catalog.