Productions

LIY(St)Y PIMF

In places where electro-magnetic interference and influence exists
Instrumentation and Control Engineering
Industrial Electronics
Computers and Office Machines
Indoor Communication Systems
Indoor Voice Systems
Security Systems

NOTES

With their flexible design they can be easily used in narrow spaces.
These cables are not suitable for outdoor installatıons.
*EMC: Electromagnetic compatibility

Conductor IEC 60228; DIN VDE 0295; EN 60228 Class 2 or Class 5 Electrolytic Bare or Tinned Copper
Insulation EN 50290-2-21 PVC Compound
Colour Code DIN 47100
Individual Screen Pes Tape + Tinned Copper Drain Wire + Pes Tape
Stranding Screened pairs in layers
Wrapping Pes Tape
Screen Tinned Copper Drain Wire + Al-Pes Tape
Sheath EN 50290-2-22 PVC Compound
Sheath Colour RAL 7001 Grey
CONDUCTOR RESISTANCE INSULATION
RESISTANCE
(500 V)
MUTUAL
CAPACITY
(MAX)
CURRENT CARRYING CAPACITY
(25°C)
OPERATING
VOLTAGE
mm²
0,22
0,34
0,50
0,75
1,0
1,5
2,5
Ω/km
79
56
39
26
19,5
13,3
7,98
0,22/0,34mm2 = 200MΩxkm
>0,50mm2= 20MΩxkm
mm²
0,22
0,34
0,50
0,75
1,0
1,5
2,5
pF/m
210
210
220
220
230
240
250
mm²
0,22
0,34
0,50
0,75
1,0
1,5
2,5
A
2,5
4,5
6,0
13
16
20
25
0,22 ve 0,34 mm² = 250 V
>0,50 mm² = 300/500 V


TEST VOLTAGE BENDING
RADIUS
TEMPERATURE
RANGE
FLAME
RETARDANT
TEST
IMPEDANCE
(APPROX.)
INDUCTANCE
(APPROX.)
0,22/0,34mm2 = 1500V
0,50mm2 = 2000V
10x Cable Ø -30ºC ~ +70ºC IEC 60332-1-2
VDE 0482-322-1-2
EN 60332-1-2
78Ω 0,67mH/km
AVESCON
2025 PRODUCT CATALOGUE
Click here to view our product catalog.
download >