(N)HXH FE180/E90
As a power and control cable;
Machine and equipment that are required to continue its function during a fire (emergency elevators, fire water pumps etc.)
Ventilation systems which are connected to fire alarm system
In emergency lighting at fire escape exits
Emergency power supplies
In places where human life and valuable materials and equipment need to be protected
| Conductor |
IEC 60228; VDE 0295; EN 60228 Class 1 or Class 2 Electrolytic Bare Copper |
| Insulation |
Cross-linked Special Polymer Compound |
| Colour Code |
VDE 0293; HD 308 S2 |
| Stranding |
In layers of optimum pitch |
| Inner Sheath |
HFFR Compound |
| Outer Sheath |
HFFR compound acc. to HD 604 S1 |
| Sheath Colour |
RAL 2003 Orange |
OPERATING
VOLTAGE (25⁰C) |
TEST VOLTAGE (50 Hz 1 Min) CORE/CORE |
BENDING RADIUS |
TEMPERATURE RANGE |
| 0,6/1kV |
4000 V |
12x Cable Ø |
- 40ºC~+90ºC |