N2XCWY

The cable is used for fixed installations such as electric power distribution networks or industrial installations, which is laid indoors, in tunnel, in cable trench or in conduit, unable to bear external mechanical force.

Rated voltage: 0.6/1(1.2)kV
Max. Permissible continuous operating temperature of conductor: 70° C
Max. Temperature of conductor during short-circuit (5s max. Duration) shall not exceed:
Nominal cross section of conductor ≤ 300mm2: 160° C;
Nominal cross section of conductor >300mm2: 140° C
The ambient temperature under installation should not be lower than: 0 ° C
The bending radius of cable is recommended as following:
For single core cable: Not less than 20 times of the diameter of cable

For multi-core cable: Not less than 15 times of the diameter of cable

 

Note: RE= round conductor RM = stranded conductor SM=sectional conductor
 
Cable size
 
Conductor type
Nominal thickness of PVC insulation(mm) Nominal thickness of PVC sheath(mm) Approx. cable overall diameter (mm) Max. D.C resistance @ 20 0 C  (Ω/km)
Phase
core
Earth
core
Phase
core
Earth
core
Phase
core
Earth
core
3x2.5+1.5mm 2 RE RE 0.8 0.8 1.8 11.7 7.41 12.1
3x4+2.5mm 2 RE RE 1.0 0.8 1.8 13.5 4.61 7.41
3x6+4mm 2 RE RE 1.0 1.0 1.8 15.0 3.08 4.61
3x10+6mm 2 RM RE 1.0 1.0 1.8 17.6 1.83 3.08
3x16+10mm 2 RM RM 1.0 1.0 1.8 20.3 1.15 1.83
3x25+16mm 2 SM RM 1.2 1.0 1.8 21.4 0.727 1.15
3x35+16mm 2 SM RM 1.2 1.0 1.8 23.1 0.524 1.15
3x50+25mm 2 SM SM 1.4 1.2 1.9 26.3 0.387 0.727
3x70+35mm 2 SM SM 1.4 1.2 2.0 30.0 0.268 0.524
3x95+50mm 2 SM SM 1.6 1.4 2.2 34.3 0.193 0.387
3x120+70mm 2 SM SM 1.6 1.4 2.3 37.6 0.153 0.268
3x150+70mm 2 SM SM 1.8 1.4 2.4 40.8 0.124 0.268
3x185+95mm 2 SM SM 2.0 1.6 2.6 45.7 0.0991 0.193
3x240+120mm 2 SM SM 2.2 1.6 2.8 51.3 0.0754 0.153
3x300+150mm 2 SM SM 2.4 1.8 2.9 56.6 0.0601 0.124