NHMH
Refineries, mines, hotels, schools, tunnels, high constructions, hospitals, power plants, data processing centers, populated business centers where there is a risk of fire.
1- Conductor : Solid or stranded copper (Class 1 or Class 2)
2- Insulation : Polypropylene (PP)
3- Filler : Halogen free flame retardant (HFFR)
4- Outer sheath : Halogen free flame retardant (HFFR)
| Min. bending radius |
12 x D |
| Max. operating temperature |
70° |
| Max. short circuit temperature |
160° |
| Rated voltage Uo/U |
300/500 V |
| AC test voltage |
2 kV |
| Low smoke |
EN 61034 |
| Halogen free |
EN 50525-1 - EN 50267 |
| Flame propagation test on single cable |
EN 60332-3-24 Cat. C |
| Nominal Cross Section mm² |
Overall Diameter mm approximately |
Net Weight kg/km approximately |
Conductor DC Resistance at (20°C) max. ohm/km |
Current Carrying Capacity in |
| Air (A) |
| H03V2V2-F (300/300 V) / 209Y |
| 2x0,50 |
5,0 |
37 |
39,0 |
3 |
| 2x0,75 |
5,5 |
46 |
26,0 |
6 |
| 3x0,50 |
5,3 |
43 |
39,0 |
3 |
| 3x0,75 |
6,3 |
61 |
26,0 |
6 |
| 4x0,50 |
5,8 |
53 |
39,0 |
3 |
| 4x0,75 |
6,4 |
68 |
26,0 |
6 |
| H05V2V2-F (300/500V) / 309Y |
| 2x0,75 |
6,3 |
57 |
26,0 |
6 |
| 2x1 |
6,6 |
65 |
19,5 |
10 |
| 2x1,5 |
7,4 |
84 |
13,3 |
16 |
| 2x2,5 |
9,1 |
130 |
7,98 |
25 |
| 2x4 |
10,4 |
179 |
4,95 |
32 |
| 3x0,75 |
6,7 |
68 |
26,0 |
6 |
| 3x1 |
7,0 |
78 |
19,5 |
10 |
| 3x1,5 |
8,1 |
106 |
13,3 |
16 |
| 3x2,5 |
9,9 |
163 |
7,98 |
25 |
| 3x4 |
11,3 |
227 |
4,95 |
32 |
| 4x0,75 |
7,3 |
82 |
26,0 |
6 |
| 4x1 |
7,9 |
100 |
19,5 |
10 |
| 4x1,5 |
9,0 |
134 |
13,3 |
16 |
| 4x2,5 |
10,8 |
201 |
7,98 |
25 |
| 4x4 |
12,3 |
280 |
4,95 |
32 |
| 5x0,75 |
8,1 |
102 |
26,0 |
6 |
| 5x1 |
8,6 |
120 |
19,5 |
10 |
| 5x1,5 |
10,0 |
166 |
13,3 |
16 |
| 5x2,5 |
12,0 |
249 |
7,98 |
25 |
| 5x4 |
13,9 |
355 |
4,95 |
32 |