NHXMH FE180/PH120
These cables which are able to continue its function during a fire are used as power and control cables at emergency and lighting systems in;| Conductor | IEC-60228; DIN VDE 0295; EN 60228 Class 1 or Class 2 Electrolytic Bare Copper |
| Insulation | Cross-linked Special polymer Compound |
| Colour Code | HD 308 S2, VDE 0293 |
| Stranding | In layers of optimum pitch |
| Inner Sheath | HFFR Compound |
| Outer Sheath | HFFR compound acc. to HD 604 S1 |
| Sheath Colour | RAL 2003 Orange |
| CONDUCTOR RESISTANCE |
INSULATION RESISTANCE (MIN) |
OPERATING VOLTAGE |
CURRENT LOAD |
BENDING RADIUS | TEST VOLTAGE | TEMPERATURE RANGE |
||
|---|---|---|---|---|---|---|---|---|
| mm² 1,5 2,5 4 6 10 16 25 |
Ω/km 12,1 7,41 4,61 3,08 1,83 1,15 0,727 |
100MΩxkm | 300/500V | mm² 1,5 2,5 4 6 10 16 25 |
A 20 25 34 44 61 82 108 |
7,5x Cable Ø | 2000 V | - 40ºC~+90ºC |