NVV(NYM)
Used in dry humid areas that there are no mechanical compulsion, under and on the plaster.
1- Conductor : Solid or stranded copper (Class 1 or Class 2)
2- Insulation : Polyvinyl chloride (PVC)
3- Filler : Polyvinyl chloride (PVC)
4- Outer sheath : Polyvinyl chloride (PVC)
| Min. bending radius |
10 x D |
| Max. operating temperature |
70° |
| Max. short circuit temperature |
160° |
| Rated voltage |
300/500 V |
| AC test voltage |
2 kV |
| Flame propagation test on single cable |
EN 60332-1 |
| Lead free |
Pb |
| Nominal Cross Section mm² |
Overall Diameter mm approximately |
Net Weight kg/km approximately |
Conductor DC Resistance at (20°C) max. ohm/km |
Current Carrying Capacity in |
| Air (A) |
| (NVV) NYM / H05VV-U, H05VV-R (300/500 V) |
| 2x1,5 |
8,8 |
121 |
12,1 |
22 |
| 2x2,5 |
10,0 |
163 |
7,41 |
30 |
| 2x4 |
10,9 |
212 |
4,61 |
40 |
| 2x6 |
11,8 |
270 |
3,08 |
51 |
| 2x10 |
15,7 |
498 |
1,83 |
70 |
| 2x16 |
18,4 |
698 |
1,15 |
94 |
| 2x25 |
20,8 |
1001 |
0,727 |
119 |
| 2x35 |
23,4 |
1320 |
0,524 |
148 |
| 3x1,5 |
8,9 |
134 |
12,1 |
16,5 |
| 3x2,5 |
10,5 |
194 |
7,41 |
23 |
| 3x4 |
11,4 |
254 |
4,61 |
30 |
| 3x6 |
12,9 |
343 |
3,08 |
38 |
| 3x10 |
16,4 |
605 |
1,83 |
52 |
| 3x16 |
18,7 |
858 |
1,15 |
69 |
| 3x25 |
22,2 |
1156 |
0,727 |
90 |
| 3x35 |
24,5 |
1500 |
0,524 |
111 |
| 4x1,5 |
9,9 |
168 |
12,1 |
16,5 |
| 4x2,5 |
11,3 |
233 |
7,41 |
23 |
| 4x4 |
10,3 |
333 |
4,61 |
30 |
| 4x6 |
14,2 |
430 |
3,08 |
38 |
| 4x10 |
18,2 |
770 |
1,83 |
52 |
| 4x16 |
20,9 |
1106 |
1,15 |
69 |
| 4x25 |
24,5 |
1468 |
0,727 |
90 |
| 4x35 |
27,2 |
1921 |
0,524 |
111 |
| 5x1,5 |
10,9 |
200 |
12,1 |
16,5 |
| 5x2,5 |
12,5 |
280 |
7,41 |
23 |
| 5x4 |
14,1 |
395 |
4,61 |
30 |
| 5x6 |
15,5 |
520 |
3,08 |
38 |
| 5x10 |
20,5 |
860 |
1,83 |
52 |
| 5x16 |
23,8 |
1300 |
1,15 |
69 |
| 5x25 |
26,8 |
1854 |
0,727 |
90 |
| 5x35 |
29,8 |
2435 |
0,524 |
111 |