RZ1-K (AS+)
Machine and equipment that are required to continue its function during a fire ( emergency elevators, fire water pumps etc.)
Ventilation systems are which are connected to fire alarm system
In emergency lighting at fire escape exits
Emergency power supplies
In places where human life and valuable materials and equipment need to be protected: hospitals, schools, museums, airport, bus terminals, shops in general, tunnels, the underground, etc., as well as in calculation centres, offices, production plants, laboratories, etc.
| Conductor |
EN 60228 Class 5 Stranded Electrolytic Plain Copper |
| Insulation |
Mica tape wrapping and Cross-linked HFFR Compound |
| Insulation Colour |
HD 308 S2 |
| Stranding |
In Layers Of Optimum Pitch |
| Sheath |
HFFR Compound according to IEC 60502-1 |
| Sheath Colour |
RAL2003 Orange |
| Available Sections |
70 mm² and above |
Insulation Colour
| 1C |
Back
|
2C
|
Blue-Brown (OB)
|
| 3C |
Yellow/Green-Blue-Brown (JB) / Brown-Black-Grey (OB) |
| 4C |
Yellow/Green-Brown-Black-Grey (JB) / Blue-Brown-Black-Grey (OB) |
5C
|
Yellow/Green-Blue-Brown-Black-Grey (JB) / Blue-Brown-Black1-Grey-Black2 (OB) |
| WORKING VOLTAGE |
TEST VOLTAGE |
MINIMUM BENDING RADIUS |
WORKING TEMPERATURE |
SHORT CIRCUIT TEMPERATURE |
INSULATION RESISTANTCE |
| 0,6/1 kV |
4000 V |
12 x Ø |
-40°C ~+90°C (Fixed Laying) |
+250ºC |
100 MΩ x km |