Productions

VG-YMvKas

Power cable for industrial applications. Suitable for underground laying and where there is mechanical compulsion.
1- Conducto : Solid or stranded copper (Class 1 or Class 2)
2- Insulation : Cross linkable polyethylene (XLPE)
3- Filler : Polyvinyl chloride (PVC)
4- Inner sheath : Polyvinyl chloride (PVC)
5- Armour : Galvanized (flat) steel wire armour with copper aerth wires and a galvanized steel tape counter helix (GSWA)
6- Outer sheath : Polyvinyl chloride (Flame retardant) (PVC-FR)
Min. bending radius 12 x D 
Max. operating temperature 90°
Max. short circuit temperature 250°
Rated voltage Uo/U 0.6/1 kV
AC test voltage 3,5 kV
Flame propagation test on single cable EN 60332-3-24 Cat. C
Lead free Pb
Cross Sectional Area mm² Class of Conductor Overall Diameter mm approximately Net Weight kg/km approximately Conductor DC Resistance at (20°C) max. ohm/km Equivalent Copper Cross Section area of Armour/PE Conductor
VG-YMvKasmb (0,6/1 kV)
 2x1,5  1  14  350  12,1 1,5
 2x2,5 15  375   7,41 2,5 
 2x4 16  445   4,61
 2x6 17  525   3,08
2x10 19  674   1,83 10 
 2x10 20  812   1,83 10 
 2x16 23  1049   1,15 16 
 2x25 26  1419   0,727 16 
 2x35 29  1800   0,524 16 
 3x1,5 15  355   12,1 1,5 
 3x2,5 15  415   7,41 2,5 
3x4 16  490   4,61
 3x6 18  590   3,08
 3x10 20  895   1,83 10 
 3x10 21  938   1,83 10 
 3x16 24  1289   1,15 16 
 3x25 27  1748   0,727 16 
 3x35 31  2087   0,524 16 
 4x1,5 1 15 390  12,1 1,5 
 4x2,5 16  465   7,41 2,5 
 4x4 17  650   4,61
 4x6 19  740   3,08
 4x10 1 21  1040   1,83 10 
 4x10 22  1093   1,83 10 
 4x16 25  1518   1,15 16 
 4x25 30  2110   0,727 16 
 4x35 2 33  2536   0,524 16 
 5x1,5 16  420   12,1 1,5
 5x2,5 17  510   7,41 2,5
 5x4 19  670   4,61 4
 5x6 20  870   3,08 6
 5x10 1 22  1165   1,83 10
 5x10 24  1327   1,83 10
 5x16 27  1785   1,15 16
5x25 2 32 2470 0,727 16
5x35 2 37 3135 0,524 16
AVESCON
2025 PRODUCT CATALOGUE
Click here to view our product catalog.