VO-YMvKasXLPE INSULATED, FLAME RETARDANT, PVC SHEATHED BRAIDING CABLES WITH PROTECTIVE EARTH CONDUCTOR
| Min. bending radius | 10 x D |
| Max. operating temperature | 90° |
| Max. short circuit temperature | 250° |
| Rated voltage Uo/U | 0.6/1 kV |
| AC test voltage | 3,5 kV |
| Flame propagation test on single cable | EN 60332-3-24 Cat. C |
| Lead free | Pb |
| Nominal Cross Section mm² | Overall Diameter mm approximately | Net Weight kg/km approximately | Conductor DC Resistance at (20°C) max. ohm/km | Current Carrying Capacity in |
|---|---|---|---|---|
| Air (A) | ||||
| VO-YMvKasmb (0,6/1 kV) | ||||
| 2x1,5+1,5 | 12,4 | 238 | 12,1 | 24 |
| 2x2,5+2,5 | 13,2 | 251 | 7,41 | 32 |
| 2x4+4 | 14,0 | 361 | 4,61 | 42 |
| 2x6+6 | 17,5 | 450 | 3,08 | 53 |
| 3x1,5+1,5 | 12,4 | 216 | 12,1 | 24 |
| 3x2,5+2,5 | 13,2 | 293 | 7,41 | 32 |
| 3x4+4 | 15,5 | 425 | 4,61 | 42 |
| 3x6+6 | 19,2 | 535 | 3,08 | 53 |
| 4x1,5+1,5 | 13,5 | 321 | 12,1 | 24 |
| 4x2,5+2,5 | 14,4 | 334 | 7,41 | 32 |
| 4x4+4 | 15,5 | 444 | 4,61 | 42 |
| 4x6+6 | 19,2 | 574 | 3,08 | 53 |