YDY 450/750V
Installation in walls, on boards and in channels or embedded in plaster.
1- Conductor : Solid copper (Class 1)
2- Insulation : Polyvinyl chloride (PVC)
3- Outer sheath : Polyvinyl chloride (PVC)
| Min. bending radius |
8 x D |
| Max. operating temperature |
70° |
| Max. short circuit temperature |
160° |
| Rated voltage |
450/750 V |
| AC test voltage |
2,5 kV |
| Flame propagation test on single cable |
EN 60332-1 |
| Min. storage temperature |
-40° |
| Lead free |
Pb |
| Nominal Cross Section mm² |
Overall Diameter mm approximately |
Net Weight kg/km approximately |
Conductor DC Resistance at (20°C) max. ohm/km |
Current Carrying Capacity in |
| Air (A) |
| CYKY (450/750 V) |
| 2x1 |
7,5 |
81 |
18,1 |
- |
| 2x1,5 |
8 |
97 |
12,1 |
15 |
| 2x2,5 |
8,8 |
125 |
7,41 |
20 |
| 2x4 |
10,1 |
176 |
4,61 |
27 |
| 2x6 |
11,1 |
228 |
3,08 |
34 |
| 3x1 |
7,9 |
96 |
18,1 |
- |
| 3x1,5 |
8,5 |
116 |
12,1 |
15 |
| 3x2,5 |
9,3 |
153 |
7,41 |
20 |
| 3x4 |
10,7 |
219 |
4,61 |
27 |
| 3x6 |
12 |
294 |
3,08 |
34 |
| 4x1 |
8,6 |
116 |
18,1 |
- |
| 4x1,5 |
9,2 |
142 |
12,1 |
15 |
| 4x2,5 |
10,1 |
190 |
7,41 |
20 |
| 4x4 |
11,9 |
279 |
4,61 |
27 |
| 4x6 |
13,1 |
369 |
3,08 |
34 |
| 4x10 |
16 |
581 |
1,83 |
46 |
| 5x1 |
9,1 |
136 |
18,1 |
- |
| 5x1,5 |
9,7 |
168 |
12,1 |
15 |
| 5x2,5 |
10,7 |
227 |
7,41 |
20 |
| 5x4 |
12,6 |
335 |
4,61 |
27 |
| 5x6 |
13,9 |
447 |
3,08 |
34 |
| 5x10 |
17 |
707 |
1,83 |
46 |