Productions

YVZ3V (NYFGBY)

Dimensions and Weights Electrical Information
Nominal
cross-section
Overall
Diameter
Net Weight Delivery 
reel size for 
1000m cable
Conductor DC (maks.) 
resistance at 
20 °C (maks.)
Current carrying capacity in
Ground(A) Air(A)
>mm >mm >kg/km >cm >ohm/km
3x16/10 rm >24,5 >1325 >140 1,15 102 79
3x25/16 rm >28,0 >1850 >160 0,727 133 100
3x35/16 rm >30,0 >2250 >160 0,524 159 125
3x50/25 rm >34,0 >2900 >180 0,387 188 153
3x70/35 rm >38,0 >3800 >210 0,268 232 195
3x95/50 rm >43,0 >4950 >230 0,193 280 238
3x120/70 rm >47,0 >6150 >240 0,153 318 275
3x150/70 rm >51,0 >7150 210* 0,124 359 320
3x185/95 rm >56,0 >8950 220* 0,0991 406 364
3x240/120 rm >62,0 >11000 240* 0,0754 473 430
3x300/150 rm >67,0 >14000 210** 0,0601 535 510
3x400/185 rm >78,0 >18000 230** 0,0470 613 595
Code YVZ3V-R (TSE), NYFGbY (VDE)
Standarts TS IEC 60502-1, VDE 0271
Construction Copper conductor, PVC insulation, PVC filler, Galvanized flat steel wire armoured, Galvanized steel tape, PVC outer sheath
Application Installation underground,indoor, in ducts and in the open air where mechanical protection is required against higher tensile stress during installation and operation.
Technical Datas Max. Operating temperature 70 °C
Max. Short circuit temperature <=300 mm² for 160 °C > 300 mm² for 140 °C
Min. Bending radius 12*D D:Cable outer diameter (mm)
AVESCON
2025 PRODUCT CATALOGUE