Supply & Distribution

Voltmann Type Mechanical Cold Water Meter

Model C
WS10-250-B12 250 175 180 x 8 PCS
WS12-250-B20 250 175 210 x 8 PCS
WS15-300-B30 300 180 240 x 8 PCS
WS20-350-B50 350 200 295 x 12 PCS
Technical Specifications WS10 250-B12 WS12 250-B20 WS15 300-B30 WS20 350-B50
Maximum Working Pressure bar  16 16 16 16
Maximum Pressure Loss at Q3 bar  0,63  0,63  0,63  0,63
Metrological Class   R80/R63  R80/R63  R80/R63  R80/R63
Installation Type   Horizontal/Vertical      
Connection Diameter   DN100  DN125  DN150  DN200
Metrological Limits ( EN 14154, OIML R49 )          
Minimum Flow Rate (Q1) m³/h 1,25/1,59  2/2,54  3,125/3,97  5/6,35
Transitional Flow Rate (Q2) m³/h 2/2,54  3,2/4,06  5/6,35  8/10,16
Permanent Flow Rate (Q3) m³/h 100 160 250 400
Overload Flow Rate (Q4) m³/h 125 200 312,5  500
Maximum Water Temperature (Tmax) ˚C 50 50 50 50
Physical Properties          
Weight kg  17 21 29 46
Protection Class - IP68  IP68  IP68  IP68
Pulse Output - Optional  Optional  Optional  Optional
AVESCON
2025 PRODUCT CATALOGUE
Click here to view our product catalog.
download >